Tel:+86-21-57468933 Fax:+86-21-57577777 Email: paul@ekcneke.cn cneke@cneke.cc
KYN28A-12 (GZS1-12Z) central metal-clad and metal-enclosed switchgear
K---------------------------------------metal-clad and metal-enclosed Switchgear
Y---------------------------------------withdrawable
N---------------------------------------Indoor
12-------------------------------------- rated voltage (KV)
□--------------------------------------primary plan No.
□--------------------------------------operating mechanism characteristic code
D: electromagnetism T: spring
□--------------------------------------rated current (A)
□--------------------------------------rated short circuit drop-out current (KA)
KYN
The shell adopts the aluminum-zinc alloy coated steel sheet, processed by CNC machining tool, which ensure the high mechanical strength. The door is anti-corrosion and anti-impact coaedt. And the protection degree is IP4X
The main switch can be with the ZN
The insulation distance is over
|
item |
Unit |
Parameters |
|||
|
rated voltage |
KV |
12 |
|||
|
rated current |
HZ |
50 |
|||
|
rated current of circuit breaker |
A |
630\2000 |
|||
|
rated current of switch cabinet |
A |
630\2000 |
|||
|
rated current of dynamic stability (4S) |
KA |
16\20\25\31.5\40\50 |
|||
|
rated current of dynamic stability (peak) |
KA |
40\50\63\80\100\125 |
|||
|
rated short circuit drop-out current |
KA |
16\20\25\31.5\40\50 |
|||
|
rated short circuit making current (peak) |
KA |
40\50\63\80\100\125 |
|||
|
Rated insulation level |
1min power frequency withstand voltage |
KA |
24 |
32 |
42 |
|
lighting impulse withstand voltage |
KA |
40 |
60 |
75 |
|
|
protection degree |
IP2X shell: IP4X, it is IP2X when compartment and circuit breaker room is open |
||||